A.FEATURES OF AGGREGATE CHILLER
  B. ESTIMATED EFFICIENCY OF VARIOUS CHILLING PROCESSES
  C. CALCULATION OF HEAT BALANCE
D. SPECIFICATIONS
  E. INSTALLATION EXAMPLE

  1. ICE WATER CHILLER (IWC)
2. CHILLER FOR THE CEMENT OF CONCRETE (CMC)
3. CHILLER FOR THE GRAVEL AGGREGATE OF CONCRETE (CAC)

4. ICE WATER AND GRAVEL CHILLER (CIAC)
  1. Ice Water Chiller for Concrete Batching Plant  

                 Model

 Item

IWC-30A

IWC-65A

IWC-100A

50Hz/60HzKcal/h

Compressor Cooling Capacity (KW)

103,800 / 124,600

   120 / 140

232,400 / 278,800

   270 / 320

333,500 / 400,200

   380 / 450

Evaporating Temperature

      0

      0

      0

Condensing Temperature

     +30

    +30

    +30

Ice Water Capacity

Water Temperature: 28 Input and 1 Output50Hz/60Hz

3.6 / 4.3 cbm/hr

8.4 / 10 cbm/hr

12 / 14.4 cbm/hr

DimensionsL×W×Hmm

3,300×2,000×2,200

4,500×2,000×2,200

6,100×2,500×2,600

 Weight

2,800Kgs

3,400Kgs

4,600Kgs

Refrigerant

     R-22

     R-22

     R-22

Compressor Motor Power Input

23.1KW×50/60Hz

49.4KW×50/60Hz

69.9KW×50/60Hz

Expansion Tank

200 liters

400 liters

600 liters

Glycol Pump

3.75KW

5.5KW

7.5KW

Ice Water Circulating Pump

3.75KW

5.5KW

7.5KW

Cooling Tower

- Cooling Pump

- Cooling Fan

50 RT

3.75KW

0.75KW

80 RT

5.5KW

1.5KW

150 RT

7.5KW

3.75KW

Total Power Consumption

36KW

68KW

97KW

 

 

 
TOP  
Copyrights © 2008 Senbo Technic Co.,Ltd. All Right Reserved
Web Designed by Lotus Business Information Co. / allitwares hi-tech alliance