4. Specifications of Ice Water and Gravel Chiller for Concrete Batching Plant |
|
Model
Item |
CIAC-100S |
CIAC-150S |
Power Source |
3 Phase – 220 V / 380 V × 60 Hz |
Normal Chilling Capacity |
300,000 Kcal/hr |
450,000 Kcal/hr |
Total Power Consumption(* Two-in-One Type ) |
119.4(*130.8) KW |
181(*203.4) KW |
Compressor |
Type |
Screw Semi-hermetic |
Quantity |
1 |
Starting Method |
Y-Δ |
Revolution |
3,550 rpm |
Output |
74 KW |
106 KW |
Crankcase Oil Heater |
150 W |
Refrigerant |
Type |
R 22 |
Quantity |
50 Kgs |
75 Kgs |
Chiller |
Type |
Shell and Tube |
Quantity |
1 |
Condenser |
Type |
Shell and Tube |
Quantity |
1 |
Cooling Tower |
Type × Quantity |
125 RT × 1 |
175 RT × 1 |
Pump |
7.5 HP × 1 |
15 HP × 1 |
Fan |
3 HP × 1 |
5 HP × 1 |
Heat Exchanger for Chilling Air |
Type |
Fin-tube |
Fin-tube |
Quantity |
50 RT × 2 |
75 RT × 2 |
Expansion Water Tank |
1,600 liter × 1 |
1,600 liter × 1 |
Glycol Pump to Air Handling Unit |
5 HP × 2 |
10 HP × 2 |
Fan of Air Handling Unit |
Air Volume × Static Pressure |
150CMM×300mmaq |
230CMM×300mmaq |
HP × Quantity |
20 HP × 2 |
30 HP × 2 |
Dimension of Air Handling Unit ( L × W × H ) mm |
3,000×2,000×2,000 |
3,300×2,000×2,000 |
Weight of Air Handling Unit |
1,800 Kgs |
2,200 Kgs |
* Ice Water Heat Exchanger |
Type |
Plate |
Plate |
Quantity |
100 RT × 1 |
150 RT × 1 |
* Glycol Pump to Ice Water Heat Exchanger |
7.5 HP × 1 |
15 HP × 1 |
* Ice Water Circulating Pump |
7.5 HP × 1 |
15 HP × 1 |
* Water Chilling Capacity |
Water Volume |
11.1 m^3/hr |
16.7 m^3/hr |
Normal / Ice Water Temperature |
28℃ / 1℃ |
28℃ / 1℃ |
Dimension without Air Handling Unit ( L × W × H ) |
6,100×2,440×2,590 mm |
Weight without Air Handling Unit |
4,600 Kgs |
5,800 Kgs |
Note:Items with * mark are for Two-in-One type.
|
|
|